Phase shifting transformer for medium voltage inverter(MVD)
- Min. Order:
- 1 Set/Sets
- Min. Order:
- 1 Set/Sets
- Transportation:
- Ocean
Your message must be between 20 to 2000 characters
Contact NowPayment Type: | T/T,L/C |
---|---|
Incoterm: | FOB |
Transportation: | Ocean |
Product Advantage:
1. Class H insulation
2. Small size, light weight
3. Built-in temperature controller, monitor and protect the transformer.
4. Excellent Conformal Coating performance can withstand thermal shock.
5, IP00 and IP54 selectable
Model no.:
Technical Specification:
No. |
Item |
Unit |
Technical Data |
Remark |
1 |
Standard |
|
IEC60076,IEC61378 GB1094.3-2003,JB/T8636-1997 |
|
2 |
Type |
|
Dry type |
|
3 |
Installation |
|
Indoor |
|
4 |
Rated power |
kVA |
Up to 10000 |
|
5 |
Rated primary voltage |
kV |
3/3.3/6/6.6/10/11 |
|
6 |
Rated Secondary voltage |
V |
690 |
|
7 |
Rated primary current |
A |
Depends on power and voltage |
|
8 |
Rated second current |
A |
Depends on power and voltage |
|
9 |
Rated frequency |
Hz |
50±0.5 |
|
10 |
Phase |
|
3 |
|
11 |
Connection |
|
D/ Trilateral triangle |
|
12 |
The second windings |
|
18 |
|
13 |
Impedance voltage |
|
7%-9% |
|
14 |
Winding Temperature Rise |
K |
125 |
|
15 |
Tapping method |
|
off-circuit |
|
16 |
Tapping range |
|
±5% |
|
17 |
Insulation level |
|
H |
|
18 |
Altitude |
m |
≤1000 |
|
19 |
Ambient temperature |
℃ |
Max 50,Min-5 |
|
20 |
Earthing |
|
—— |
|
21 |
Cooling |
|
AF |
|
22 |
Primary insulation level |
KV |
28 |
|
Secondary insulation level |
kV |
20 |
|
|
23 |
Efficiency |
|
98% |
|
24 |
Material of winding |
|
oxygen-free copper |
|
25 |
Material of core |
|
Silicon sheet |
|
26 |
Material of insulation |
|
H class Material of insulation |
|
27 |
Safety standard |
|
IP00/IP54 |
|
28 |
Accessories |
|
Temperature controller, cooling fans |
|
Product Dimension:
Will be provided according to the requirement: Capacity, primary voltage, secondary voltage, IP degree, etc.