Why Need Refrigerated Air Dryer
The compressed air used in the industrial field contains a lot of moisture, which will not only cause product defects, but also shorten the service life of the equipment. Therefore, it is very important to use clean and pure compressed air without water.
The Refrigerated Air Dryer is one of the necessary equipment to remove the moisture in the compressed air condensed by the compressor in the industrial field.
The refrigerated air dryer adopts aluminum alloy plate heat exchanger, environmentally friendly refrigerant and micro-computer automatic control, which can visually display the dew point temperature of the dryer; it has multiple protections of temperature and pressure. And inside compressor air dryer installed four pieces of high efficiency compressed air filters with an electronic condensate drain, when install and maintain, it is much more convenient.

The following products are suitable for use at 220V 50HZ, 380V 50Hz voltage, other voltages can be customize.
Model | Flow Rate (m³/min) | Power Supply | Input Power (kw) | Air line Connection | Refrigerant Type | G.W.(kg) | Measurement (mm) |
HL010 | 1.2 | 220V 50Hz | 0.37 | RC3/4" | R134a | 34 | 480*380*665 |
HL020 | 2.4 | 220V 50Hz | 0.52 | RC3/4" | R134a | 42 | 520*410*725 |
HL030 | 3.6 | 220V 50Hz | 0.73 | RC 1" | R410a | 50 | 580*460*785 |
HL060 | 6.5 | 220V 50Hz | 1.26 | RC 1 1/2" | R410a | 63 | 700*540*910 |
HL080 | 8.5 | 220V 50Hz | 1.87 | RC 2" | R410a | 73 | 770*590*990 |
HL100 | 11.0 | 220V 50Hz | 2.43 | RC 2" | R410a | 85 | 770*590*990 |
HL120 | 13.5 | 220V 50Hz | 2.63 | RC 2" | R410a | 94 | 800*610*1030 |
HL150 | 17.0 | 380v 50Hz | 3.00 | DN50 Flange | R407c | 180 | 1000*850*1143 |
HL200 | 23.0 | 380v 50Hz | 3.70 | DN65 Flange | R407c | 210 | 1100*900*1203 |
HL250 | 27.0 | 380v 50Hz | 5.80 | DN80 Flange | R407c | 350 | 1200*950*1273 |
HL300 | 33.0 | 380v 50Hz | 6.10 | DN80 Flange | R407c | 420 | 1450*1000*1350 |
HL400 | 42.0 | 380v 50Hz | 8.00 | DN100 Flange | R407c | 550 | 1550*1100*1403 |
HL500 | 55.0 | 380v 50Hz | 9.20 | DN100 Flange | R407c | 680 | 1680*1300*1600 |
HL600 | 65.0 | 380v 50Hz | 10.10 | DN100 Flange | R407c | 780 | 1750*1450*1680 |
HL800 | 85.0 | 380v 50Hz | 12.00 | DN125 Flange | R407c | 920 | 1950*1500*1900 |

Working Conditions & Technical Requirements
Rated ambient temperature: 38 ° C, max.42 ° C.
Rated inlet temperature: 38 ° C, max. 65 ° C.
Rated air pressure: 0.7Mpa, max. 1.6Mpa.
Pressure dew point under rated conditions: 2 ° C ~ 10 ° C (atmospheric dew point: -23 ° C ~-17 ° C).
Assembly environment: no sun, no rain, and good ventilation, installed in a horizontal hard foundation, no obvious dust and flying flour.