Aa Aaa Rechargeable 2V100AH Batteries
- Payment Type:
- L/C, T/T, D/P
- Incoterm:
- FOB, CFR, CIF
- Min. Order:
- 100 Piece/Pieces
- Min. Order:
- 100 Piece/Pieces
- Delivery Time:
- 30 Days
- Transportation:
- Ocean, Land
Your message must be between 20 to 2000 characters
Contact NowPlace of Origin: | china |
---|---|
Productivity: | 2000, 000kvah/ Year |
Supply Ability: | 2000, 000kvah/ Year |
Payment Type: | L/C,T/T,D/P |
Incoterm: | FOB,CFR,CIF |
Certificate: | iso,UL,CE |
Transportation: | Ocean,Land |
Reserve GEL Battery CFPG2100,capacity :2V100Ah batteries is Sealed Lead Acid Battery. The values for the upper edge of the curves were obtained from charging at an ambient temperature of +20℃ with a voltage limit to 2.30V/Cell. For the lower
edge, charging was carried out at the specified ambient temperature. The curves show the behavior of battery
after a number of cycles.
can be used for just about every application, including: UPS Backup Systems, Alarm Systems, Fire Alarm Systems, Medical Equipment, Test Equipment, and much more.
Specifications
Nominal Voltage |
2 V |
||
Capacity (25℃) |
10HR(1.80V) |
100Ah |
|
3HR(1.75V) |
76.5Ah |
||
1HR(1.75V) |
56.5Ah |
||
Dimension |
Length |
171±2mm (6.73inch) |
|
Width |
72±1mm (2.83inch) |
||
Height |
205±2mm (8.07inch) |
||
Total Height |
208±2mm (8.19inch) |
||
Approx. Weight |
5.8kg (12.8lbs)±4% |
||
Terminal type |
T11 |
||
Internal resistance (Fully charged, 25℃) |
Approx. 1.1mΩ |
||
Capacity affected by temperature (10HR) |
40℃ |
102% |
|
25℃ |
100% |
||
0℃ |
85% |
||
-15℃ |
65% |
||
Self-discharge (25℃) |
3 month |
Remaining Capacity: 91% |
|
6 month |
Remaining Capacity: 82% |
||
12 month |
Remaining Capacity: 65% |
||
Nominal operating temperature |
25℃±3℃(77℉±5℉) |
||
Operating temperature range |
Discharge |
-15℃~50℃(5℉~122℉) |
|
Charge |
-10℃~50℃(14℉~122℉) |
||
Storage |
-20℃~50℃(-4℉~122℉) |
||
Float charging voltage(25℃) |
2.25 to 2.30V Temperature compensation: -3mV/℃ |
||
Cyclic charging voltage(25℃) |
2.40 to 2.45V Temperature compensation: -5mV/℃ |
||
Maximum charging current |
20A |
||
Terminal material |
Copper |
||
Maximum discharge current |
800A(5 sec.) |
||
Designed floating life(20℃) |
18~20 years |
◆ Gelled electrolyte technology;
◆ PVC separator;
◆ Recognized by UL & CE;
◆ ABS container.
Constant Current Discharge Characteristics (A, 25℃)
F.V/TIME |
15min |
30min |
60min |
2h |
3h |
4h |
5h |
6h |
8h |
10h |
20h |
1.60V |
110 |
85.0 |
60.0 |
36.5 |
26.0 |
20.9 |
18.2 |
15.6 |
12.2 |
10.2 |
5.34 |
1.65V |
107 |
83.3 |
58.8 |
36.3 |
25.9 |
20.8 |
18.0 |
15.5 |
12.2 |
10.2 |
5.33 |
1.70V |
105 |
81.6 |
57.6 |
36.0 |
25.7 |
20.6 |
17.9 |
15.4 |
12.1 |
10.1 |
5.32 |
1.75V |
102 |
80.0 |
56.5 |
35.5 |
25.5 |
20.5 |
17.8 |
15.3 |
12.0 |
10.1 |
5.29 |
1.80V |
98.2 |
77.5 |
54.7 |
34.6 |
24.7 |
19.9 |
17.3 |
14.8 |
11.6 |
10.0 |
5.25 |
Constant Power Discharge Characteristics (Watt, 25℃)
F.V/TIME |
15min |
30min |
60min |
2h |
3h |
4h |
5h |
6h |
8h |
10h |
20h |
1.60V |
201 |
159 |
114 |
70.5 |
51.0 |
41.0 |
35.8 |
30.7 |
24.4 |
20.3 |
10.7 |
1.65V |
195 |
156 |
112 |
70.1 |
50.7 |
40.7 |
35.6 |
30.6 |
24.2 |
20.2 |
10.7 |
1.70V |
191 |
153 |
109 |
69.5 |
50.3 |
40.5 |
35.3 |
30.4 |
24.0 |
20.2 |
10.6 |
1.75V |
187 |
150 |
107 |
68.4 |
50.0 |
40.2 |
35.1 |
30.1 |
23.9 |
20.0 |
10.6 |
1.80V |
180 |
145 |
104 |
66.7 |
48.5 |
39.0 |
34.0 |
29.2 |
23.2 |
19.9 |
10.5 |
Note: The above characteristics data can be obtained within three charge/discharge cycles.
ISO9001 approval, FN: Q3105105131
ISO14001 CTC04912E10302ROM
OHS MS18001 04912S10150ROM
UL approval, FN:MH28204
CE approval, FN:G2M20201-0102-E-16
KS approval, FN:KS C 8519
VDS approval
BS approval
FP Series Battery General Features
- Nonspillable
- Sealed and Maintenance-free Operation
- High Quality and High Reliability
- Exceptional Deep Discharge Recovery
- Low Self-discharge
- Long Service Life
- Solid Copper Terminals
- Tank-formed Plates
- Computer-aided Design and Manufacturing
- UL, CE, VdS Approved
Typical Applications
- Telecommunication equipment
- Electronic instruments
- Fire alarm
- Security devices
- UPS power supply
- Emergency lighting