Lithium Rechargeable Batteries 2V
- Payment Type:
- L/C, T/T, D/P
- Incoterm:
- FOB, CFR, CIF
- Min. Order:
- 100 Piece/Pieces
- Min. Order:
- 100 Piece/Pieces
- Delivery Time:
- 30 Days
- Transportation:
- Ocean, Land
Your message must be between 20 to 2000 characters
Contact NowPlace of Origin: | china |
---|---|
Productivity: | 2000, 000kvah/ Year |
Supply Ability: | 2000, 000kvah/ Year |
Payment Type: | L/C,T/T,D/P |
Incoterm: | FOB,CFR,CIF |
Certificate: | iso,UL,CE |
Transportation: | Ocean,Land |
CFPV2800
THE FP12120L BATTERY is desgined for general purpose and long life, focus on improving trickle life that base on FP series. Main features as follow:
When it is used in safe surroundings, the battery is maintenance free, no need adding water and it can be recharged repeatedly.
ü With isolated seal, it can be put in horizontal way, vertical way and side way, its safety and functions totally will not be affected.
ü With special formula to manufacture lead calcium alloy as well as automatic progresses, gassing will be less.
ü Long life, low self-discharge rate and high reliability.
ü It has safety, low resistance so recharge is easy and energy output is more remarkable.
ü Container material could be frame retardant ABS or PP with ranking UL 94V-0 by model.Where to Buy Batteries
ü Standby use.
ü High rate discharge construction.
ü Deep discharge recoverability.
ü Batteries are strictly tested by our patented computer charge/discharge system.
ü ISO9001, 14001, OHSMS 18001 certified.
ü UL recognized components under UL 1989 (file number MH14533).
ü Complies with IATA/ICAO Special Provision A67 for air transport.
ü Classified per MG Amendment 27 as a non-hazardous material for water transport.
ü Recognized by DOT as "Dry charge" 49 CFR 171-189 for surface transport.
International certifications:
- ISO9001 approval, FN: Q3105105131
- ISO14001 CTC04912E10302ROM
- OHS MS18001 04912S10150ROM
- UL approval, FN:MH28204
- CE approval, FN:G2M20201-0102-E-16
- KS approval, FN:KS C 8519
- VDS approval
- BS approval
General Features
- Nonspillable
- Sealed and Maintenance-free Operation
- Front terminal,convenience for facilitate testing and servicing.
- High Quality and High Reliability
- Exceptional Deep Discharge Recovery
- Low Self-discharge
- Long Service Life
- Solid Copper Terminals
- Tank-formed Plates
- Computer-aided Design and Manufacturing
- UL, CE, VdS Approved
Typical Applications
-
1.UPS and EPS
2.Emergency lightp
3.Railway signal and aircraft signal system
4.Marine and power stations
5.Alarm and security system;
6.Electronic apparatus and equipment
7.Communication power supply, DC power supply
Specifications
Nominal Voltage |
2 V |
||
Capacity (25℃) |
10HR(1.80V) |
800 Ah |
|
3HR(1.75V) |
624Ah |
||
1HR(1.75V) |
429Ah |
||
Dimension |
Length |
210±2mm (8.27inch) |
|
Width |
191±2mm (7.52inch) |
||
Height |
646±3mm (25.43inch) |
||
Total Height |
681±3mm (26.81inch) |
||
Approx. Weight |
58.3kg (128.5bs)±5% |
||
Terminal type |
T10 |
||
Internal resistance (Fully charged, 25℃) |
Approx. 0.35mΩ |
||
Capacity affected by temperature (10HR) |
40℃ |
102% |
|
25℃ |
100% |
||
0℃ |
85% |
||
-15℃ |
65% |
||
Self-discharge (25℃) |
3 month |
Remaining Capacity: 93% |
|
6 month |
Remaining Capacity: 85% |
||
12 month |
Remaining Capacity: 72% |
||
Nominal operating temperature |
25℃±3℃(77℉±5℉) |
||
Operating temperature range |
Discharge |
-15℃~50℃(5℉~122℉) |
|
Charge |
-10℃~50℃(14℉~122℉) |
||
Storage |
-20℃~50℃(-4℉~122℉) |
||
Float charging voltage(25℃) |
2.25 to 2.30V Temperature compensation: -3mV/℃ |
||
Cyclic charging voltage(25℃) |
2.30 to 2.35V Temperature compensation: -5mV/℃ |
||
Maximum charging current |
160A |
||
Terminal material |
Copper |
||
Maximum discharge current |
3200A(5 sec.) |
||
Designed floating life(20℃) |
20 years |
◆ Gelled electrolyte technology;
◆ Tubular Positive Plate;
◆ ABS container.
Constant Current Discharge Characteristics (A, 25℃)
F.V/TIME |
30min |
60min |
2h |
3h |
4h |
5h |
6h |
8h |
10h |
20h |
24h |
48h |
72h |
100h |
120h |
1.60V |
680 |
456 |
276 |
212 |
171 |
146 |
126 |
98.7 |
81.4 |
43.2 |
37.2 |
19.7 |
13.4 |
9.87 |
8.40 |
1.65V |
666 |
449 |
274 |
211 |
170 |
145 |
125 |
98.2 |
81.3 |
43.1 |
37.1 |
19.7 |
13.4 |
9.84 |
8.38 |
1.70V |
646 |
438 |
272 |
209 |
169 |
144 |
124 |
97.5 |
81.0 |
43.0 |
36.9 |
19.6 |
13.3 |
9.81 |
8.35 |
1.75V |
630 |
429 |
268 |
208 |
168 |
143 |
123 |
96.8 |
80.6 |
42.7 |
36.8 |
19.5 |
13.2 |
9.75 |
8.30 |
1.80V |
607 |
416 |
261 |
202 |
163 |
139 |
120 |
93.9 |
80.0 |
42.4 |
36.6 |
19.4 |
13.2 |
9.68 |
8.24 |
Constant Power Discharge Characteristics (Watt, 25℃)
F.V/TIME |
30min |
60min |
2h |
3h |
4h |
5h |
6h |
8h |
10h |
20h |
24h |
48h |
72h |
100h |
120h |
1.60V |
1272 |
866 |
533 |
416 |
336 |
288 |
248 |
195 |
162 |
86.3 |
74.8 |
39.9 |
27.5 |
20.2 |
17.2 |
1.65V |
1246 |
853 |
530 |
413 |
334 |
286 |
246 |
194 |
162 |
86.2 |
74.6 |
39.8 |
27.4 |
20.2 |
17.2 |
1.70V |
1208 |
832 |
525 |
411 |
332 |
284 |
244 |
193 |
161 |
85.9 |
74.1 |
39.6 |
27.3 |
20.1 |
17.1 |
1.75V |
1179 |
815 |
517 |
408 |
329 |
282 |
243 |
192 |
160 |
85.4 |
73.9 |
39.4 |
27.1 |
20.0 |
17.0 |
1.80V |
1136 |
790 |
504 |
395 |
319 |
274 |
235 |
186 |
159 |
84.8 |
73.6 |
39.1 |
26.9 |
19.8 |
16.9 |
Note: The above characteristics data can be obtained within three charge/discharge cycles.
data can be obtained within three charge/discharge cycles.
Related Keywords