High Temperature VRLA Battery
- Payment Type:
- L/C, T/T, D/P
- Incoterm:
- FOB, CFR, CIF
- Min. Order:
- 100 Piece/Pieces
- Min. Order:
- 100 Piece/Pieces
- Delivery Time:
- 30 Days
- Transportation:
- Ocean, Land
Your message must be between 20 to 2000 characters
Contact NowPlace of Origin: | china |
---|---|
Productivity: | 2000, 000kvah/ Year |
Supply Ability: | 2000, 000kvah/ Year |
Payment Type: | L/C,T/T,D/P |
Incoterm: | FOB,CFR,CIF |
Certificate: | iso,UL,CE |
Transportation: | Ocean,Land |
Specifications
Nominal Voltage
12 V
Capacity
(25℃)
10HR(10.8V)
7.0Ah
3HR(10.8V)
5.25Ah
1HR(10.5V)
3.85Ah
Dimension
Length
151±1.5mm (5.94inch)
Width
65±1mm (2.56inch)
Height
94±1mm (3.70inch)
Total Height
100±1mm (3.94inch)
Approx. Weight
2.35kg (5.18lbs)±5%
Terminal type
T1/T2
Internal resistance
(Fully charged, 35℃)
Approx. 28mΩ
Capacity affected by temperature (20HR)
50℃
104%
25℃
100%
0℃
75%
-20℃
51%
Nominal operating temperature
20℃~35℃
Operating temperature range
Discharge
-15℃~70℃(5℉~158℉)
Charge
-10℃~70℃(14℉~158℉)
Storage
-20℃~70℃(-4℉~158℉)
Float charging voltage(35℃)
13.30 to 13.60V
Temperature compensation:
-18mV/℃
Equalization charge voltage(35℃)
13.80 to 14.40V
Temperature compensation:
-18mV/℃
Cyclic charging voltage(35℃)
14.50 to 14.70V
Temperature compensation:
-30mV/℃
Maximum charging current
1.75A
Terminal material
Copper
Maximum discharge current
105A(5 sec.)
Designed floating life(35℃)
3-5 years
◆ Absorbent glass mat technology;
◆ Recognized by UL & CE;
◆ Suitable for higher temperature enviroment.
◆ABS container.
Constant Current Discharge Characteristics (A, 25℃)
F.V/TIME |
5min |
10min |
15min |
30min |
60min |
2h |
3h |
4h |
5h |
10h |
20h |
9.60V |
26.2 |
16.5 |
12.9 |
7.23 |
4.09 |
2.56 |
1.84 |
1.58 |
1.34 |
0.73 |
0.386 |
9.90V |
25.4 |
16.0 |
12.6 |
7.01 |
4.03 |
2.55 |
1.83 |
1.56 |
1.33 |
0.72 |
0.383 |
10.2V |
24.3 |
15.4 |
12.2 |
6.84 |
3.96 |
2.53 |
1.81 |
1.55 |
1.32 |
0.72 |
0.380 |
10.5V |
23.3 |
14.7 |
11.9 |
6.64 |
3.88 |
2.50 |
1.80 |
1.54 |
1.31 |
0.71 |
0.375 |
10.8V |
22.0 |
13.9 |
11.4 |
6.28 |
3.73 |
2.43 |
1.75 |
1.50 |
1.27 |
0.70 |
0.368 |
Constant Power Discharge Characteristics (Watt, 25℃)
F.V/TIME |
5min |
10min |
15min |
30min |
60min |
2h |
3h |
4h |
5h |
10h |
20h |
9.60V |
292 |
186 |
148 |
82.8 |
47.4 |
30.0 |
21.9 |
18.7 |
16.0 |
8.74 |
4.60 |
9.90V |
283 |
181 |
144 |
80.3 |
46.7 |
29.8 |
21.7 |
18.6 |
15.9 |
8.70 |
4.55 |
10.2V |
272 |
173 |
140 |
78.4 |
45.8 |
29.6 |
21.6 |
18.5 |
15.8 |
8.66 |
4.53 |
10.5V |
260 |
166 |
136 |
76.1 |
44.9 |
29.2 |
21.4 |
18.4 |
15.6 |
8.47 |
4.53 |
10.8V |
245 |
157 |
130 |
71.9 |
43.2 |
28.4 |
20.8 |
17.8 |
15.2 |
8.43 |
4.36 |
Note: The above characteristics data can be obtained within three charge/discharge cycles.
ISO9001 approval, FN: Q3105105131
ISO14001 CTC04912E10302ROM
OHS MS18001 04912S10150ROM
UL approval, FN:MH28204
CE approval, FN:G2M20201-0102-E-16
KS approval, FN:KS C 8519
VDS approval
BS approval
Typical Applications
Fire alarm systems
Solar lighting equipment
Outdoor telecommunication equipment
Related Keywords