Shenzhen Sunray Power Co., Ltd.
Shenzhen Sunray Power Co., Ltd.
1K~3K ONLINE UPS / Power supply with double conversion mode
  • 1K~3K ONLINE UPS / Power supply with double conversion mode
1K~3K ONLINE UPS / Power supply with double conversion mode

1K~3K ONLINE UPS / Power supply with double conversion mode

Delivery Time:
20 Days
Quantity:

Your message must be between 20 to 2000 characters

Contact Now
Basic Info
Basic Info
Place of Origin: Guangdong, China (Mainland)
Product Description
Product Description
Specifications ONLINE UPS

1,INPUT:110V/220V OUTPUT:110V/220V

2,LCD/LED DISPLAY

1K~20K ONLINE  UPS   Key Features Wide input voltage range Zero transfer time Smart RS232 communication interface Sealed lead-acid, maintenance free battery  True on-line double conversion technology with advanced microprocessor control Technical Specifications

Product Series

BS

Model

BS1K/1KS

BS2K/1KS

  BS3K/1KS

Rated Power

VA/W

1kVA / 0.7kW

2kVA / 1.4kW

3kVA / 2.1kW

Input

Nominal Voltage

110VAC/220VAC

Voltage Range

60~138VAC/115 ~ 300VAC

Frequency Range

46~54Hz(default), user adjustable within 40~60Hz

Power Factor

0.97

Output

Voltage

110VAC/220VAC ± 2%

Frequency

46~54Hz or 50Hz ± 0.2Hz (Line mode)
50Hz ± 0.2Hz ( Battery mode)

Waveform

Sine Wave

Distortion

3%

4%

Overload Capability

108%~150% for 30 sec., ±150% for 300 ms

Current Crest Ratio

3:1

Battery

Type

Sealed, Maintenance free, Lead-Acid (Panasonic)

Recharge Time

5 hrs to 90% of capacity after full load discharge

Bypass 

 

Automatic Transfer

on overload and UPS failure

Before UPS Power-on

Default “NO”, user adjustable to “YES”

Voltage Range

80~264VAC (Default), user adjustable within 80~286VAC

Transfer Time

0 ms; less than 4 ms from inverter to bypass and vice versa

LED/LCD

Indicators

Status

Load level / Battery level, Battery , Utility Power, Inverter, Bypass, Overload, Fault

Audible Alarm

Bypass, On battery mode, Battery low, Overload, Fault

Acoustic Noise

At 1 meter distance

45 dBA

50 dBA

Communications

DB-9 Port

RS-232 Serial Interface

Intelligent Slot

Options: WebPower, AS400 Card or WinPower CMC

Environmental

OperatingTemperature

0 ~ 40°C

Operating Humidity

20 ~ 90% non-condensing

Weight

Net (Kg)

14/7

34/13.5

34.5/14

Dimensions

W x D x H (mm)

145*400*220

192*460*340

1K~3KONLINE  UPS