Product Description


Pure Sine Wave Line Interactive UPS 2000va 3000va 5000va with LED Display
1. Accurate pure sine wave output; strongly compatible with different loads;
2. Wide range of input and accurate output;
3.Smart RS232 communication port;
4. Perfect protection for overload, short circuit,over-voltage,low-voltage and over-heating etc;
5. LED Indicator;
6. UPS restart automatically when the main power recovers (optional);
7. Built-in super smart charger, shorten 50% of charging time;
8. Charging ability at low input voltage, 2 times more powerful than other.

Applications:
- High quality and availability of energy adapted to suit specific critical needs- Covering a vast range of applications. Applied to key devices.- Communication system.- Computer network system.- Some devices need harsh electric power environment.
Specifications:
Note:”L” means long back up model &“M” means standard model with inbuilt battery..

Model

2000M/2000L

3000M/3000L

5000M/5000L

Capacity

VA/W

2000VA/1400W

3000VA/2100W

5000VA/3500W

INPUT

Voltage

100/110/120/127/220/230(± 25%) VAC

Frequency(HZ)

60/50±10%


Output

Crest factor

3:1

Voltage

100/110/120/127/220/230 (Auto-sensing)

Voltage Regulation

±10%

Frequency

50HZ or 60HZ

Frequency Regulation

±0.5%

Output Waveform

Pure sine wave

Protection

Overload

UPS automatically shut down if overload exceeds
120% of normal value
for 30 seconds and 150% for 3 seconds.

Short circuit

UPS output cut off immediately or input circuit breaker protection


Alarm

Battery back-up

Beeping 4 times every minute when the input cut off

Battery low voltage

Beeping every 1 second

Overload

Audible alarm

INDICATOR

LED Display

Red: broken-down indicator; Green: commercial power indicator;
Yellow: inversion/charge indicator; load level; battery level.


BATTERY

Type

Sealed, maintenance-free lead acid

DC voltage

24VDC


48VDC

Battery (standardard model ”M”)


12V 17AH*2 pcs

12V 17AH*2 pcs

12V 17*AH*4 pcs

Backup time

Standard model: half load≥8mins;Long back up model:
decided by external batteries

Recharge Current

Standard model: MAX 3A; Long back up time mode: MAX 15A

Protection

Automatic self-test, discharge protection, over-charging protection,
smart management system.

Communication
interface(optional)

Compatible system

Supports Windows® 98/2000/2003/XP/Vista/2008,
Windows® 7, Linux, and MAC

Port(Standard)

RJ 11/RJ 45

Port(Optional)

RS 232/USB

Physical

“M” Dimension D*W*H(mm)

465*190*350

460*190*350

585*190*350

“M” Net Weight(kg)

31.8

34

51.8

“L” Dimension D*W*H(mm)

465*190*350

465*190*350

465*190*350

“L” Net Weight(kg)

23

25

28.5

ENVIRONMENT

Operating Environment

0- 40°C,0-90% relative humidity(non-condensing)

Noise Level(within 1 meter)

Less than 45DB


Competitive Advantage:
1. Excellent Microprocessor Control Design Guarantees the high reliability;
2. Boost and Buck AVR for stabilizing input power voltage;
3. Built-in DC start function for starting up itself without AC input power;
4. RS232 interface Communication Port for transmitting UPS real-time conditions and remote control;
5. Winpower, free software available online for ups real-time monitoring and controlling.